du/dt Filters Installation Guide
5
du/dt Filters Installation Guide
Contents
This document contains the following information:
General notes and restrictions
Technical data (including allowable ambient conditions)
Internal circuit diagrams
Power connection diagrams
Filter selection tables
Dimensional drawings (including terminal sizes and tightening torques).
General notes and restrictions
Observe the following before you start to install the du/dt filters:
WARNING! Do not attempt any work on a powered drive. After switching off the
mains, always allow the intermediate circuit capacitors 5 minutes to discharge before
working on the frequency converter, the motor or the motor cable. It is good practice
to check (with a voltage indicating instrument) that the drive is in fact discharged
before beginning work.
Unprotected (IP00) filters must be encased to meet the local safety requirements.
The surface of the IP22/IP54 filter housing can reach a temperature up to 40 °C
higher than the ambient temperature.
Shielded cable must be used between enclosures.
Filters must be grounded to the protective earth (PE) by using the fixing holes in
the mounting legs.
Maximum drive output frequency: 120 Hz
Maximum average switching frequency:
3 kHz (converter units with supply voltage <
500 V) or
2 kHz (converter units with supply voltage > 500 V)
Maximum cable length between the drive output and the filter: 3 m
Maximum motor cable length for AOCH0xxx-70 filters: 300 m (cumulative for
several parallel-connected motors)