Technical data 121
Efficiency
Approximately 98% at nominal power level
The efficiency is not calculated according to the ecodesign standard
IEC 61800-9-2.
Energy efficiency data (ecodesign)
Energy efficiency data according to IEC 61800-9-2 is available from the
ecodesign tool (https://ecodesign.drivesmotors.abb.com).
Cooling
Method Internal fan, flow direction from front to top
Free space around the
unit
Refer to
ACS800-04/04M/U4 Cabinet Installation
[3AFE68360323
(English)].
Cooling air flow See
IEC data
(page 99).
Degrees of protection
IP00 (UL type: open chassis)
Prevention of unexpected start-up (+Q950): AGPS-21
board
Nominal input voltage 115 V AC or 230 V AC
Input voltage range
(selected by jumper)
95...132 V AC (X3 on), 185...265 V AC (X4 on, default)
Nominal frequency 50/60 Hz
Current 0.77 A at 115 V, 0.44 A at 230 V
Max. external fuse 16 A
Input connector X1
3× 2.5mm
2
User connector 1, 2, 3
600 V, 25 A, 0.5...4 mm
2
(20...12 AWG)
Output voltage 24 V +
0.5 V
Nominal output current 1.7 A (50 °C, 122 °F)
X2 terminal block type JST B3P-VH
Ambient temperature 0...50 °C (32...122 °F)
Relative humidity 30...90%, no condensation allowed
Approvals CE, C-UL US listed