EasyManua.ls Logo

ABB ACS850-04 - Technical Data; What this Chapter Contains; Ratings

ABB ACS850-04
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
125
Technical data
What this chapter contains
This chapter contains the technical specifications of the drive, for example, the
ratings, sizes and technical requirements, provisions for fulfilling the requirements for
CE and other markings.
Ratings
The ratings of the drive modules with 400 V, 460 V and 500 V (50 Hz and 60 Hz)
supply are given below.
Drive type
ACS850-04
Frame
size
Input
rating
Output ratings
Nominal use Light-overload use Heavy-duty use
I
1N
I
max
I
2N
P
N
I
Ld
P
Ld
I
Hd
P
Hd
AAAkWhpAkWhpAkWhp
U
N
= 400 V
-387A-5 G1 380 470 387 200 - 377 200 - 300 160 -
-500A-5 G1 490 560 500 250 - 480 250 - 355 200 -
-580A-5 G1 570 680 580 315 - 570 315 - 414 200 -
-650A-5 G1 640 730 650 355 - 634 355 - 477 250 -
-710A-5 G2 690 850 710 400 - 700 400 - 566 315 -
-807A-5 G2 790 1020 807 450 - 785 450 - 625 355 -
-875A-5 G2 860 1100 875 500 - 857 450 - 680 400 -
U
N
= 500 V
-387A-5 G1 380 470 387 200 - 377 250 - 300 160 -
-500A-5 G1 490 560 500 250 - 480 250 - 355 250 -
-580A-5 G1 570 680 580 355 - 570 355 - 414 250 -
-650A-5 G1 640 730 650 400 - 634 400 - 477 315 -
-710A-5 G2 690 850 710 500 - 700 500 - 566 400 -
-807A-5 G2 790 1020 807 560 - 785 560 - 625 450 -
-875A-5 G2 860 1100 875 560 - 857 560 - 680 450 -
U
N
= 460 V
-387A-5 G1 380 470 387 - 300 377 - 300 300 - 200
-500A-5 G1 490 560 500 - 350 480 - 350 355 - 250
-580A-5 G1 570 680 580 - 450 570 - 450 414 - 350
-650A-5 G1 640 730 650 - 500 634 - 500 477 - 400
-710A-5 G2 690 850 710 - 600 700 - 600 566 - 450
-807A-5 G2 790 1020 807 - 700 785 - 600 625 - 500
-875A-5 G2 860 1100 875 - 700 857 - 700 680 - 600
3AXD00000581898
I
1N
Nominal input current (rms) at 40 °C (104 °F)
I
max
Maximum output current. Available for 10 seconds at start, otherwise as long as allowed by drive
temperature.
I
2N
Continuous rms output current. No overload capability at 40 °C (104 °F)

Table of Contents

Other manuals for ABB ACS850-04

Related product manuals