EasyManua.ls Logo

ABB ACS850-04 - Units Without Optional Cabling Panels (no +H381 or +H383); Terminal Data for the Control Cables; Electrical Power Network Specification; Motor Connection Data

ABB ACS850-04
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
130
Units without optional cabling panels (no +H381 or +H383)
In units without optional cabling panels (option +H381/+H383 not selected), it is
possible to use the maximum cable size (4 × (3 × 240) mm2 or 4 × [3 × 500 AWG])
only with special cable lugs and additional insulation. For more information, contact
your local ABB representative.
Terminal data for the control cables
See page 104.
Electrical power network specification
Voltage (U
1
) 380...500 VAC 3-phase ± 10%
Rated conditional short-
circuit current (IEC 60439-1)
65 kA when protected by fuses given in the fuse tables
Frequency 48 to 63 Hz, maximum rate of change 17%/s
Imbalance Max. ± 3% of nominal phase to phase input voltage
Fundamental power factor
(cos phi
1
)
0.98 (at nominal load)
Motor connection data
Motor types asynchronous AC induction motors, permanent magnet motors, ABB synchronous
reluctance motors (SynRM motors)
Voltage (U
2
) 0 to U
1
, 3-phase symmetrical, U
max
at the field weakening point
Frequency DTC mode: 0 to 3.2 · f
f
. Maximum frequency 500 Hz (120 Hz with du/dt or sine filter). Low
motor noise mode is recommended with high frequencies (see also firmware manual).
f
f
=
f
f
: frequency at field weakening point; U
N
: electrical power system voltage; U
m
: nominal
motor voltage; f
m
: nominal motor frequency
Frequency resolution 0.01 Hz
Current See section Ratings.
Nominal motor frequency 0…500 Hz
Switching frequency 3 kHz (typically)
Maximum recommended
motor cable length
DTC control Scalar control
300 m (984 ft) 300 m (984 ft)
Note: Motor cable longer than 100 m (328 ft) is allowed but then the EMC Directive
requirements of Category C3 may not be fulfilled.
Brake resistor connection data
See page 159.
U
N
U
m
· f
m

Table of Contents