Planning the electrical installation
57
Typical power cable sizes
The table below gives copper and aluminium cable types with concentric copper 
shield for the drives with nominal current. See also Terminal and lead-through data 
for the power cables on page 129. 
1) The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type 
trays one on top of the other, ambient temperature 30 °C (86 °F), PVC insulation, surface 
temperature 70 °C (158 °F) (EN 60204-1 and IEC 60364-5-52). For other conditions, dimension the 
cables according to local safety regulations, appropriate input voltage and the load current of the 
drive.
2) The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 
40 °C (104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or 
cable or earth (directly buried). For other conditions, dimension the cables according to local safety 
regulations, appropriate input voltage and the load current of the drive.
Drive type
ACS850-04
IEC 
1)
US 
2)
Cu cable type Al cable type Cu cable type Al cable type
mm
2
mm
2
AWG/kcmil AWG/kcmil
-387A-5 2 × (3×120) 3 × (3×120) 2 × 250 MCM 2 × 350 MCM
-500A-5 3 × (3×95) 3 × (3×150) 2 × 500 MCM or 3 × 250 MCM 2 × 600 MCM or 3 × 300 MCM
-580A-5 3 × (3×120) 3 × (3×185) 2 × 500 MCM or 3 × 250 MCM 2 × 700 MCM or 3 × 350 MCM
-650A-5 3 × (3×150) 3 × (3×240) 2 × 600 MCM or 3 × 300 MCM 3 × 400 MCM or 4 × 250 MCM
-710A-5 3 × (3×185) 4 × (3×185) 2 × 700 MCM or 3 × 350 MCM 3 × 500 MCM or 4 × 300 MCM
-807A-5 3 × (3×240) 4 × (3×240) 3 × 500 MCM or 4 × 300 MCM 3 × 600 MCM or 4 × 400 MCM
-875A-5 3 × (3×240) 4 × (3×240) 3 × 500 MCM or 4 × 300 MCM 3 × 700 MCM or 4 × 500 MCM
3BFA 01051905 D