Safety instructions
16
Permanent magnet motor drives
These are additional warnings concerning permanent magnet motor drives.
WARNING! Ignoring the instructions can cause physical injury or death, or damage
to the equipment.
Do not work on the drive when the permanent magnet motor is rotating. Also,
when the supply power is switched off and the drive is stopped, a rotating
permanent magnet motor feeds power to the intermediate circuit of the drive and
the supply connections become live.
Before installation and maintenance work on the drive:
Stop the motor.
Ensure that there is no voltage on the drive power terminals according to step 1 or
2, or if possible, according to the both steps.
1. Disconnect the motor from the drive with a safety switch or by other means.
Measure that there is no voltage present on the drive input, output or DC
terminals (U1, V1, W1, U2, V2, W2, UDC+, UDC-).
2. Ensure that the motor cannot rotate during work. Make sure that no other system,
like hydraulic crawling drives, is able to rotate the motor directly or through any
mechanical connection like felt, nip, rope, etc. Measure that there is no voltage
present on the drive input, output or DC terminals (U1, V1, W1, U2, V2, W2,
UDC+, UDC-). Ground the drive output terminals temporarily by connecting them
together as well as to the PE.