Parameters 303
Warning/Fault If the drive is modulating, the external event generates a fault.
Otherwise, the event generates a warning.
3
31.03 External event 2
source
Defines the source of external event 2. See also parameter
31.04 External event 2 type.
For the selections, see parameter 31.01 External event 1
source.
Inactive
(true); DIIL
(95.20 b5)
31.04 External event 2
type
Selects the type of external event 2.
Fault The external event generates a fault. 0
Warning The external event generates a warning. 1
Warning/Fault If the drive is modulating, the external event generates a fault.
Otherwise, the event generates a warning.
3
31.05 External event 3
source
Defines the source of external event 3. See also parameter
31.06 External event 3 type.
For the selections, see parameter 31.01 External event 1
source.
Inactive
(true)
31.06 External event 3
type
Selects the type of external event 3.
Fault The external event generates a fault. 0
Warning The external event generates a warning. 1
Warning/Fault If the drive is modulating, the external event generates a fault.
Otherwise, the event generates a warning.
3
31.07 External event 4
source
Defines the source of external event 4. See also parameter
31.08 External event 4 type.
For the selections, see parameter 31.01 External event 1
source.
Inactive
(true)
31.08 External event 4
type
Selects the type of external event 4.
Fault The external event generates a fault. 0
Warning The external event generates a warning. 1
Warning/Fault If the drive is modulating, the external event generates a fault.
Otherwise, the event generates a warning.
3
31.09 External event 5
source
Defines the source of external event 5. See also parameter
31.10 External event 5 type.
For the selections, see parameter 31.01 External event 1
source.
Inactive
(true)
31.10 External event 5
type
Selects the type of external event 5.
Fault The external event generates a fault. 0
Warning The external event generates a warning. 1
Warning/Fault If the drive is modulating, the external event generates a fault.
Otherwise, the event generates a warning.
3
31.11 Fault reset
selection
Selects the source of an external fault reset signal. This
signal will be observed even if it is not the active source in the
current control location (EXT1/EXT2/Local).
(A reset from the active source will be observed regardless of
this parameter.)
0
>
1 = Reset
Not selected
Not selected 0. 0