DescriptionExample valueNameIndex
Sets the SLS1 positive speed limit that trips
the drive.
250 rpmSLS1 trip limit posit-
ive
SLSx.14
Adjust the default value to meet the motor
in use.
Note: The difference between the SLS trip
limit and the corresponding SLS limit
(200.23 SLS1 limit positive) must be at least
0.1 rpm.
Sets the digital output that is connected to
the primary output of the SLS1 function.
Active when the SLS monitoring is on.
DO X114:8SLS1 output ASLSx.15
For option +Q965, ABB has configured the
SLS indication signal to this digital output at
the factory.
SAR1 ramp settings
Sets the target time for the stop ramp SAR1
that is used in the SLS function. Adjust the
default value when necessary.
2000 msSAR1 ramp time to
zero
200.112
Target time = The time in which the drive
decelerates the motor(s) from speed
200.202 SAR speed scaling to zero.
Note: With value 0 ms, the drive uses the
emergency stop ramp set by drive paramet-
er 23.23. In this case, the FSO module also
monitors the actual ramp (ramp monitoring
or time monitoring).
Time monitoring: This value has no effect
in the operation. The drive (parameter 23.13
Deceleration time 1 or 23.15 Deceleration
time 2) defines the deceleration ramp.
Ramp monitoring: Adjust the default value
when necessary.
The same value is used for SAR0 and SAR1
ramps. See section SAR0 ramp settings.
1500 rpmSAR speed scaling200.202
The same value is used for SAR0 and SAR1
ramps. See section SAR0 ramp settings.
100 msSAR initial allowed
range
SARx.02
Sets the minimum ramp time for the SAR1
ramp monitoring.
1000 msSAR1 min ramp time
to zero
SARx.21
Time monitoring: This value has no effect
in the operation.
Ramp monitoring: Sets the minimum decel-
eration time for the emergency stop. Adjust
the default value when necessary.
Note: With value 0 ms, the ramp is not
monitored.
Sets the maximum ramp time for the SAR1
ramp monitoring.
3000 msSAR1 max ramp time
to zero
SARx.22
Time monitoring: This value has no effect
in the operation.
Ramp monitoring: Sets the maximum decel-
eration time for the emergency stop. Adjust
the default value when necessary.
Parameter settings 45