SSM1 function is shown as an example. ABB has activated the SSM1 function at the factory.
For more information, see FSO-21 module user’s manual.
DescriptionExample valueNameIndex
Activates or deactivates the SSM1 function
and shows the version of the SSM1 function.
Version 1SSM1 activity and
version
SSMx.01
Disabled: Deactivates the SSM1 function.
Version 1: Activates the SSM1 function.
For option +Q965, ABB has activated the
SSM1 function at the factory. Adjust the
value if necessary.
Sets the digital input connected to the SSM1
function.
Always onSSM1 inputSSMx.11
Always on: The SSM1 function is always
on. No external request signal is needed to
activate the SSM1 function.
For option +Q965, ABB has configured the
SSM1 function to be “Always on” at the
factory.
Sets the negative speed limit for the SSM1
function.
-100 rpmSSM1 limit negativeSSMx.12
Sets the positive speed limit for the SSM1
function.
100 rpmSSM1 limit positiveSSMx.13
Sets the digital output connected to the
SSM1 function.
DO X113:8SSM1 outputSSMx.14
Active when the motor speed is within the
SSM1 speed limits.
For option +Q965, ABB has configured the
SSM1 indication signal to this digital output
at the factory.
Sets the diagnostic pulse of digital output
X113:8 on or off.
OnDO X113:8 diag
pulse on/ off
SAFEIO.55
On: The output monitors that it receives test
pulses.
Sets the logic state of digital output X113:8.Active highDO X113:8 logic
state
SAFEIO.72
Active high: The digital output is on when
the indicated signal is active.
For option +Q965, ABB has configured the
SSM1 indication signal to this digital output
at the factory.
Make sure that this value corresponds to
the actual wiring. See the circuit diagrams
of the delivery.
■ FSE-31 module and safety pulse encoder related parameters
Set these parameters when you use a safety pulse encoder in the safety application.
DescriptionExample valueNameIndex
Activates the FSE-31 encoder interface and
shows the version of the encoder parameter
groups (91 and 92).
Version 1FSE 3X act and par
version
200.231
Shows the number of safety encoders con-
nected to the FSE-31 module.
Single encoder CH1Number of encoders200.232
Parameter settings 47