23
The available energy capacity depends now on the criteria for the U
dc,lim
and
the actual DC link voltage supplied into common DC system. Selection of the
value for U
dc,lim
depends on common DC system configuration and its
general requirements.
Here are the major alternatives for the U
dc,lim
based on the ACSM1 drive
module DC voltage limits (see also the paragraph ACSM1 DC voltage
limits).
Absolute maximum limit is defined according to the DC overvoltage trip
limit including some safety margin.
840
,limdc
U V DC
DC over voltage control is enabled, but not activated.
810
lim,dc
U V DC
DC link voltage level, where the braking choppers are not yet
activated.
780
,limdc
U V DC
To determine whether the energy capacity is adequate (i.e. the selected
U
dc,lim
voltage level is not reached) the following condition must be fulfilled
W
dc
> E
gen
Where E
gen
is the regenerative energy to the DC link during the generating
period:
dtPE
gengen
=