13
Instructions for the assemblage and the use
3. Technical characteristics
Power supply voltage
[V] 230 AC ±10%
Frequency
[Hz] 50/60
Max input signal value
AMTD-1 P, AMTD-1-R P [A] 5 AC
VLMD P, VLMD-R P [V] 600 AC/DC
AMTD-2 P, AMTD-2-R P [mV] 60 DC
Full scale values available
on AMTD-1 P and AMTD-1-R P
[A] Indirect insertion by means of CT …/5A
15 20 25 40 60 100 150 200 250 400 600 999
Full scale values available
on AMTD-2 P and AMTD-2-R P
[A] Indirect insertion by means of shunt 60mV
15 20 25 40 60 100 150 200 250 400 600 999
Measurement range
AMTD-1 P, AMTD-1-R P [A] 0…999 AC
VLMD- P, VLMD-R P [V] 0…600 AC/DC
AMTD-2 P, AMTD-2-R P [A] 0…999 DC
Accuracy class
AMTD-1 P, AMTD-1-R P [%] 0,5 ±1 digit
AMTD-2 P, AMTD-2-R P [%] 0,5 ±1 digit
VLMD P, VLMD-R P [%] 0,5 ±1 digit
Memory
EEprom
Power consumption
[VA] 4