EasyManua.ls Logo

ABB AP100 Series - Water Supply for Water Wash Systems

ABB AP100 Series
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
2 INSTALLATION
Fig. 2.5 Location of Water Wash Nozzle
Sensor
Water Wash
Nozzle
Liquid
Junction
Note. It is advisable to use a
suitable hose clamp.
Fig. 2.4 Installing the Water Wash Water Supply
Install a suitable solenoid valve to
the mains water supply feed.
Connect a suitable length of
1
/4
in. i.d. p.v.c. tube to the outlet of the
solenoid valve. This tube terminates at the electrode installation point.
Push the quick-fit
connector supplied, onto
the free end of the tube.
Note that the quick-fit
connector incorporates a
cut-off valve.
To water supply – see
Important Note and
Caution, above.
Suitable Solenoid Valve (user supplied)
2
1
3
2.2 Water Supply for Water Wash Systems
Fig. 2.4 and 2.5
Important Note. Installation must only be carried
out in accordance with the local water authority and
council bylaws.
Caution. The maximum water pressure at the
electrode should not exceed 4 bar. At NO time should the
sample pressure be allowed to exceed that of the water
wash water supply. Fit a non return valve if this possibility
exists.
Information. As all quick-fit connectors used in
Water Wash systems incorporate cutoff valves, tubes
may subsequently be disconnected on operational
equipment without sample loss or water wash discharge.
Note. For optimum performance of the Water Wash
function in flow systems, the sample pressure should be
at least 2 bars lower than that of the water wash water
supply.
The water supply for the water wash system must come from a
suitable supply via a solenoid valve. The general specification
for the solenoid valve is:
Brass body: 2/2, NC
Orifice size: 3.0 / 4.0 mm
Port size:
1
/8" –
1
/4" BSP
Pressure: 0 to 6 bar
Coil: 110/115 V a.c. or 230/240 V a.c. 50/60 Hz
Before fitting the electrode cartridge system, install the water
supply as shown in Fig. 2.3.
Note. See Fig. 2.4 for recommended tubing.