20 AWT210 PROFIBUS PA 2-WIRE TRANSMITTER | COM/AWT210/PROFIBUS-EN REV. A
…8 PROFIBUS slots
Analog input blocks – slots 5 and 6
AI_1 mapping is located on slot 5. AI_2 mapping is located on slot 6.
The initial index is 16 and this number must be added to the relative
Index in column index to get the absolute index.
Index
Parameter Access Data Type Size
(bytes)
Range
STANDARD PARAMETERS
BLOCK_OBJECT R Record
ST_REV R Simple
TAG_DESC RW Simple OctetString
STRATEGY RW Simple
ALERT_KEY RW Simple
TARGET_MODE RW Simple
MODE_BLK R Record
ALARM_SUM R Record
BATCH R/W Record
STANDARD AI BLOCK PARAMETERS
NULL_ // reserved by PI
OUT RW Record
PV_SCALE RW Array Float
OUT_SCALE RW Record
LIN_TYPE RW Simple
CHANNEL RW Simple
NULL_ // reserved by PI
PV_FTIME RW Simple Float
FSAFE_TYPE RW Simple
FSAFE_VALUE RW Simple Float
ALARM_HYS RW Simple Float
NULL_ // reserved by PI
HI_HI_LIM RW Simple Float
NULL_ // reserved by PI
HI_LIM RW Simple Float
NULL_ // reserved by PI
LO_LIM RW Simple Float
NULL_ // reserved by PI
LO_LO_LIM RW Simple Float
NULL_ // reserved by PI
HI_HI_ALM R Record
HI_ALM R Record
LO_ALM R Record
LO_LO_ALM R Record
SIMULATE RW Record
OUT_UNIT_TEXT RW Simple OctetString