INSTRUCTION MANUAL
Low voltage capacitors CLMD
Installation, operation and maintenance
instructions
es
fr
it
nl
pt
se
Condensadores de potencia de baja tensión CLMD
Instrucciones de Instalación, Utilización y Mantenimiento
Condensateurs de puissance basse tension CLMD
Instructions d’installation,d’utilisation et d’entretien
Condensatori di potenza Bassa tensione CLMD
Istruzioni per l‘installazione, l‘uso e la manutenzione
Laagspanning energiecondesatoren CLMD
Installatie-, gebruiks- en onderhoudsaanwijzingen
Capacitor de potência em baixa tensão CLMD
Instruções para instalação, utilização e manutenção
Lågspänningskondensatorer för faskompensering CLMD
Anvisningar för installation, användning och underhåll
Question and Answer IconNeed help?

Do you have a question about the ABB CLMD and is the answer not in the manual?

ABB CLMD Specifications

General IconGeneral
Operating Temperature-25 °C to +55 °C
Frequency50 Hz / 60 Hz
Enclosure ProtectionIP20
TypeAutomatic, Fixed
DisplayLCD
Accuracy±1%
Protection ClassIP20

Summary

Safety and Precautions

Pre-Installation Safety

Wait 5 min after isolating supply and short-circuit terminals before handling capacitor units.

Inspection on Reception

Verify unit data, check for damage, and notify ABB of any issues immediately.

Storage Guidelines

Store in dry, dust-free, non-corrosive environments, protected from vibrations and shocks.

Transportation and Handling

Position panels with fixation points at the bottom for severe transport conditions.

Installation Procedures

Applicable Standards and Protection

Follow IEC 60831, local regulations, and check IP ratings for specific CLMD models.

Installation Environment and Use

Indoor installation with temperature limits and air circulation needs for optimal performance.

Mounting Orientations

Mount vertically or horizontally ensuring natural airflow from bottom to top with proper spacing.

Cubicle Installation Guidelines

Optimize cubicle cooling by managing component placement and airflow paths.

CLMD13 Group Assembly

Unit Fixation

Secure each CLMD unit using fixation slots and appropriate hardware.

Electrical Connections

Power Supply Connections

Use correctly sized cables and lugs, apply specified torque to terminals for power supply.

Earthing Procedures

Connect earthing via M8 terminal or enclosure fixation points with specified torque.

Harmonics Considerations

Take precautions for installations on networks with harmonic distortion and resonance risks.

Commissioning

Accessories

Interconnection Bars

Optional bars for parallel connection of CLMD13 units, for groups of two units.

Maintenance