ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/4,
1
/2 DIN and fieldmount 10 Specification
IM/CM/ED–EN Rev. X 101
Accuracy (% of reading)
Linear Inputs Standard Analog Input
CM30 / CM50 CMF310
Millivolts
Milliamps
Volts
Resistance (low)
Resistance (high)
0 to 150 mV
0 to 45 mA (CM30 and CMF310)
0 to 50 mA (CM50)
0 to 25 V
0 to 550
0 to 10 k
0.1 % or ±20 µV
0.2 % or ±4 µA
0.2 % or ±20 mV
0.2 % or ±0.1
0.5 % or ±10
0.1 % or ±20 µV
0.2 % or ±10 µA
0.2 % or ±20 mV
0.2 % or ±1
0.1 % or ±5
Sample Interval 125 ms per sample
Digital Inputs
Type Volt-free or 24 V
Minimum pulse duration Analog inputs 1 and 2:
Single inputs configured – 250 ms
Both inputs configured as analog or digital – 500 ms
Analog inputs 3 and 4:
Single inputs configured – 250 ms
Both inputs configured as analog or digital – 500 ms
Consider analog inputs 1 / 2 and 3 / 4 independently
Volt-free Contact open > 10 M / contact closed < 100 k
Frequency input*
Frequency range
1-signal
0-signal
0 to 6000 Hz
15 to 30 V
–3 to 5 V
*For use with devices with open collector outputs