Page #9 background imageLoading...
Page #9 background image
Overview 9
Auxiliary contact class
Rated continuous current
Insulation test voltage
Rated short- time withstand current
Breaking capacity (110 V ≤ Ue ≤ 250 V)
1
10 A
2000 V/1 min 50 Hz
100 A/30 ms
440 W
1.3 Main technical parameters
1.4 Auxiliary contacts
6NO6NC auxiliary contacts are available on the
contactor for the customer’s use, with the
following characteristics.
1.5 Compliance with Standards
ConVac contactors comply with the Standards of
the major industrialized countries and in particular
with the following standards:
GB/T 14808
IEC 62271-106
1.6 Protection against short-circuit
The value of the short-circuit current at the
installation site could exceed the breaking capacity
of the contactor. End-user is responsible for
protecting the contactor against short circuit
through installation of fuses or other means.
Fuse replacement must only be carried out
by qualified personnel.
Technical parameters
Rated voltages (Ur)
Rated short-duration power frequency
withstand voltage (Ud ) 50/60 Hz
Rated lightning impulse withstand voltage (Up)
Rated frequency ( fr)
Rated operational current ( Ie )
Short-time withstand current Ik (4 s)
Rated peak current (Ip)
Overload withstand current Ik (1 s)
Overload withstand current Ik (30 s)
Short-circuit breaking capacity
Short circuit making capacity
Short circuit breaking current ( Isc )-combined with fuses
Rated short-circuit making current ( Ima )-combined with fuses
category of use
Rated duty
Mechanical life
Opening time
Closing time
Ultimate performances for back-to-back capacitors banks
Operating temperature
Weight
2
Overall dimenstions
Unit
kV
kV (1 min)
kV peak
Hz
A
A
kA peak
A
A
kA
kAp
kA
kA
Cycles/hour
Cycles
Cycles
ms
ms
ms
A
kA
Hz
kg
mm
mm
mm
ConVac 7 ConVac 7/P
7.2
30
60
50-60
400
4000
10
6000
2400
5
12.5
50
130
AC-4
1200
1,000,000
100,000
70...150
15...35
40...70
C2
250
8
2500
ConVac 12 ConVac 12/P
12
42
75
50-60
400
4000
10
6000
2400
5
12.5
50
130
AC-4
1200
1,000,000
100,000
70...150
15...35
40...70
C2
160
8
2500
Electrical latched
Mechanical latched
Electrical latched
Mechanical latched
Rated current
Max. transient current of the capacitor
Max. transient frequency of the capacitor
H
W
D
-15...+40
1
15
380
342
231
50
652
530
658
20
405
342
256
60
652
530
658
1For higher temperature please contact ABB.
2Reference value, Actual weight differ due to configuration.