Starting Up the Gas Analyzer  97 
 
6  The following status messages are active during the heating-up 
phase: 
"Operating temperature": the temperature of the detector has not yet 
reached the threshold. 
"Flame error": the flame has not yet ignited. 
"Temperature limit value 1, 2": the temperature of the detector (T-
Re.D) and possibly of the heated sample gas connection (T-Re.E) is 
over or below the upper or lower limit value 1 (2). 
"Pressure limit value 1, 2": the pressure at one of the internal 
pressure regulators for instrument air (inlet, outlet), combustion 
air (air) or combustion gas (H2) is over or below the upper or lower 
limit value 1 (2). 
7  As soon as the temperature of the detector reaches the threshold 
value (150 °C), the corresponding solenoid valve in the analyzer 
automatically switches off the instrument air. The negative pressure 
regulation and the combustion air regulation attempt to adjust the 
pressures to the respective setpoint.  
The sample gas begins to flow through the analyzer after the 
instrument air is connected. 
8  After the pressures have been adjusted to the respective setpoint, the 
respective solenoid valve in the analyzer automatically connects the 
combustion gas. The combustible gas regulation attempts to adjust 
the pressure to the setpoint. 
Adjust the controlled variables of the internal pressure 
regulators 
If the analyzer is not automatically put into service with the pressure 
values specified in the analyzer data sheet, the controlled variables of 
the internal pressure regulators must be adjusted. If the controlled 
variables of the internal pressure regulators deviate, the inlet 
pressures of the instrument air, combustion air and combustion gas 
must be adjusted. 
9  Instrument air: use the external pressure regulator to set the 
controlled variable for outlet to approx. 60 % (max. 70 %). 
Controlled variable too high  reduce pressure. 
Controlled variable too low  increase pressure. 
(The controlled variable for inlet depends on the sample gas flow 
rate.) 
10  Combustion air: use the external pressure regulator to set the 
controlled variable for air to approx. 55 % (max. 60 %). 
Controlled variable too high  increase pressure. 
Controlled variable too low  reduce pressure. 
11  Combustion gas: use the external pressure regulator to set the 
controlled variable for H2 to approx. 42 % (max. 52 %) . 
Controlled variable too high  increase pressure. 
Controlled variable too low  reduce pressure.