EasyManua.ls Logo

ABB NEXUS Series - Environmental and Operating Conditions

ABB NEXUS Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NEXUS Series | Detailed engineering specifications
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
14
ENVIRONMENTAL AND OPERATING CONDITIONS
Ingress protection rating
IP50
Temperature range
Operating (with a maximum temperature
gradation of 15°C per hour)
0°C
50°C (32°F
122°F) when connected to a 24
V AC/DC power source.
0°C
40°C (32°F
10F) when connected to a
power adapter.
Note: The maximum operating temperature
is derated 1°C/305 m (1000 ft) above
sea level altitude.
Non-operating
(with a maximum temperature gradation of
15°C per hour)
-40°C
70°C (-40°F
158 °F)
Relative humidity (maximum):
Operating
(with maximum humidity gradation of 10%
per hour)
10%
90% (non-condensing)
Non-operating
(with maximum humidity gradation of 10%
per hour)
5%
95% (non-condensing)
Altitude (maximum, unpressurized):
Operating
-15.20 m
5000 m (-50 ft
16,404 ft)
Note: The maximum operating temperature
is derated 1°C/305 m (1000 ft) above
sea level altitude.
Storage
-15.20 m
10,668 m (-50 ft
35,000 ft)

Related product manuals