Technical data
21
Technical data
Nominal voltage: 380 … 690 V ± 10%.
Rated short-time withstand current: 50 kA 1 s.
Applicable standards and markings: EN 60204-1, EN 60529, EN 61800-3,
EN 50178, CE marking, UL approval.
Ambient conditions, operation
Air temperature: -15 to +50 °C. At temperatures from +40 °C to +50 °C, the rated
output current is decreased by 1% for every additional 1
°C. The output current is
calculated by multiplying the current given in the rating table by the derating factor.
Relative humidity: 5% to 95%, no condensation allowed. Maximum allowed relative
humidity is 60% in the presence of corrosive gases.
Installation site altitude: 0 to 4000 m. At altitudes from 1000 to 4000 m above the
sea level, the rated output current is decreased by 1% for every 100 m.
Vibration:
AOCH0xxx-70: Max 1 mm (5 to 13.2 Hz), max 7 m/s
2
(13.2 to 100 Hz) sinusoidal
(IEC 60068-2)
NOCH0xxx-6x: Max 0.3 mm (2 to 9 Hz), max 1 m/s
2
(9 to 200 Hz) sinusoidal
(IEC60068-2)
Shock: Max 70 m/s
2
, 22 ms (IEC 60068-2-27)
Ambient conditions, storage
Temperature: -40 to +70 °C.
Relative humidity: Less than 95%, no condensation allowed
Atmospheric pressure: 70 to 106 kPa
Vibration:
AOCH0xxx-70: Max 1 mm (5 to 13.2 Hz), max 7 m/s
2
(13.2 to 100 Hz) sinusoidal
(IEC 60068-2)
NOCH0xxx-6x: Max 0.3 mm (2 to 9 Hz), max 1 m/s
2
(9 to 200 Hz) sinusoidal (IEC
60068-2)
Shock: Max 100 m/s
2
, 11 ms (IEC 60068-2-27)
Ambient conditions, transportation
Ambient transportation conditions refer to the conditions du/dt filters are subjected to
during transportation in the protective package.
Temperature: -40 to +70
°C