EasyManua.ls Logo

ABB PSE18 - Page 50

ABB PSE18
192 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...

FR
Paramètre de base recommandé
Ventilateur centrifuge 10 s OFF 40 % 5,0 x I
e
OFF OFF
Ventilateur axial 10 s OFF 40 % 5,0 x I
e
OFF OFF
Pompe centrifuge 10 s 10 s 40 % 5,0 x I
e
OFF On
Pompe haute pres-
sion
10 s 10 s 50 % 5,5 x I
e
OFF On
Compresseur 5 s OFF 40 % 4,5 x I
e
OFF OFF
Broyeur 10 s OFF 40 % 5,0 x I
e
OFF OFF
Mélangeur 10 s OFF 40 % 5,0 x I
e
OFF OFF
Moteur d'étrave 10 s OFF 40 % 4,5 x I
e
OFF OFF
Pompe hydraulique 10 s OFF 40 % 4,5 x I
e
OFF OFF
Broyeur 10 s OFF 40 % 5,0 x I
e
OFF OFF
Convoyeur à bande 10 s OFF 50 % 5,0 x I
e
OFF OFF
Escalator 10 s OFF 40 % 4,5 x I
e
OFF OFF
Ascenseur 10 s OFF 40 % 4,5 x I
e
OFF OFF
Dispositif de coupe
10 s OFF 40 % 5,0 x I
e
OFF OFF
Scie à ruban 10 s OFF 40 % 5,0 x I
e
OFF OFF
Scie circulaire 10 s OFF 40 % 5,0 x I
e
OFF OFF
Notez que les valeurs des paramètres ci-dessus sont données à titre indicatif uniquement. Un


et de la
limite de courant
peut s'avérer nécessaire.
Tableau 6.2 : Paramètres de l'application