Settings and configuration
Chapter 7
81
1SFC132003M0201
7:1.2 Parameter list
Param.
number
Description Display text Setting range Default
value
Actual
setting
1 Setting current Setting Ie 9.0...1207A Individual
2 Start ramp Start Ramp 1...30s, 1...120s 10s
3 Stop ramp Stop Ramp 0...30s, 0...120s 0s
4 Initial voltage Init Volt 30...70% 30%
5 End voltage End volt 30...70% 30%
6 Step down voltage Step down 30...100% 100%
7 Current limit Current Lim 2.0...7.0xle 4.0xle
8 Kick start Kick Start Yes, No No
9 Kick start level Kick Level 50...100% 50%
10 Kick start time Kick Time 0.1...1.5s 0.2s
11 Start ramp range Start Range 1-30s, 1-120s 1-30s
12 Stop ramp range Stop Range 0-30s, 0-120s 0-30s
13 Overload protection type Overload No, Normal, Dual Normal
14 Overload protection class OL Class 10A, 10, 20, 30 10
15 Overload class, dual type, start class OL Class S 10A, 10, 20, 30 10
16 Overload class, dual type, run class OL Class R 10A, 10, 20, 30 10
17 Overload protection, type of operation OL Op Stop-M, Stop-A, Ind Stop-M
18 Locked rotor protection Locked Rotor Yes, No No
19 Locked rotor protection level Lock R Lev 0.5...8.0xle 4.0xle
20 Locked rotor protection time Lock R Time 0.2...10s 1.0s
21 Locked rotor protection, type of operation Lock R Op Stop-M, Stop-A, Ind Stop-M
22 Underload protection Underload Yes, No No
23 Underload protection level Underl Lev 0.4...0.8xle 0.5xle
24 Underload protection time Underl Time 1...30s 10s
25 Underload protection, type of operation Underl Op Stop-M, Stop-A, Ind Stop-M
26 Phase imbalance protection Phase Imb Yes, No No
27 Phase imbalance protection level Ph Imb Lev 10...80% 80%
28 Phase imbalance protection, type of opera-
tion
Ph Imb Op Stop-M, Stop-A, Ind Stop-M
29 High current protection High I Yes, No No
30 High current protection, type of operation High I Op Stop-M, Stop-A, Ind Stop-M
31 Phase reversal protection Phase Rev Yes, No No
32 Phase reversal protection, type of operation Ph Rev Op Stop-M, Stop-A, Ind Stop-M
33 PTC protection PTC Yes, No No
34 PTC protection, type of operation PTC Op Stop-M, Stop-A, Ind Stop-M
35 External by-pass Ext ByPass Yes, No No
37 High current warning Warn I=High Yes, No No
38 High current warning level Wa I=H Lev 0.5...5.0xle 1.2xle
39 Low current warning Warn I=Low Yes, No No
40 Low current warning level Wa I=L Lev 0.4...1.0xle 0.8xle
41 Overload warning Warn OL Yes, No No
42 Overload warning level Wa OL Lev 40...99% 90%
43 Thyristor (SRC) overload warning Warn SCR OL Yes, No No
44 Phase loss fault, type of operation Ph Loss Op Stop- M, Stop-A Stop-M
45 Fieldbus fault, type of operation FB Fault Op Stop- M, Stop-A Stop-M
46 Frequency fault, type of operation Freq F Op Stop- M, Stop-A Stop-M
47 Heat sink over-temperature fault, type of
operation
HS Temp Op Stop- M, Stop-A Stop-M
48 Thyristor short circuit fault, type of operation SCR SC Op Stop- M, Stop-A Stop-M
49 Function of programmable input In0 In0 None, Reset, Enable
Jog, DOL, Start 2, FB-
Dis
Reset