Protections
Parameter name Setting range Default value
13.1 EOL mode
Normal/Dual
Normal
13.2 EOL class
10 A, 10, 20, 30
10
13.3 EOL dual class
10 A, 10, 20, 30
20
13.5 EOL operation Off, Stop-Manual,
Stop-Automatic, Indication
Stop-Manual
13.10 Locked rotor operation Off, Stop-Manual,
Stop-Automatic, Indication
Off
14.5 Current underload operation Off, Stop-Manual,
Stop-Automatic, Indication
Off
15.4 Over voltage operation Off, Stop-Manual,
Stop-Automatic, Indication
Off
15.7 Under voltage operation Off, Stop-Manual,
Stop-Automatic, Indication
Off
16.2 Phase reversal operation Off, Stop-Manual,
Stop-Automatic, Indication
Off
16.9 By-pass open operation Off, Stop-Manual,
Stop-Automatic, Indication
Indication
18.5 Earth fault trip time 0,1s ... 10,0s 0,5s
18.7 Earth fault operation Off, Stop-Manual,
Stop-Automatic, Indication
Off
Warnings
Parameter name Setting range Default value
20.1EOL level 40 ... 99% 90%
20.3 EOL warning On/Off Off
20.7 Locked rotor On/Off Off
20.9 Thyristor overload On/Off Off
21.5 Current underload On/Off Off
22.4 Over voltage On/Off Off
22.8 Under voltage On/Off Off
23.1 EOL time-to-trip On/Off Off
23.4 THD(U) level 1...10% 10%
23.6 THD(U) On/Off Off
24.1 Number of starts limit 1 ... 65535 65535
24.3 Number of starts On/Off Off
23.8 Short circuit On/Off Off