1SFC132081M0201 | Installation and commissioning manual | Functions 137
Parameter
number
Description Setting range Number of
decimals
Fieldbus
ID
Default value Actual
setting
12.22 Fieldbus AI 1 None, Phase L1 current, Phase L2 current,
Phase L3 current, Active power (HP), Active
power, Apparent power, Mains voltage,
Power factor, Motor voltage, Active energy
(resettable), EOL time to trip, Mains frequency,
Max phase current, Motor current, Motor
run time (resettable), Motor temperature,
Motor temperature percent, Number of
starts (resettable), Phase sequence, PT100
temperature, PTC resistance, Reactive energy
(resettable), Reactive power, Remaining time
to start, Thyristor temperature, Thyristor
temperature percent, EOL time to cool, Top
event code, Motor current percent, Thyristor
run time (resettable), Motor connection
Phase L1 current (high range)
Phase L2 current (high range)
Phase L3 current (high range)
Active power (HP) (high range)
Active power (high range)
Apparent power (high range)
Reactive power (high range)
Max phase current (high range)
Motor current (high range), Active energy (high
range), Reactive energy (high range) *** ***
0 168 Phase L1
current
12.23 Fieldbus AI 2 0 ... 43 *** *** 0 169 Phase L2
current
12.24 Fieldbus AI 3 0 ... 43 *** *** 0 172 Phase L3
current
12.25 Fieldbus AI 4 0 ... 43 *** *** 0 174 Max phase
current
12.26 Fieldbus AI 5 0 ... 43 *** *** 0 177 Mains
frequency
12.27 Fieldbus AI 6 0 ... 43 *** *** 0 178 Motor voltage
12.28 Fieldbus AI 7 0 ... 43 *** *** 0 179 Motor
temperature
percent
12.29 Fieldbus AI 8 0 ... 43 *** *** 0 180 Number
of starts
(resettable)
12.30 Fieldbus AI 9 0 ... 43 *** *** 0 183 Motor run time
(resettable)
12.31 Fieldbus AI 10 0 ... 43 *** *** 0 186 Top event code
13 Protections list 1
13.01 EOL mode Normal, Dual 0 55 Normal
13.02 EOL class 10A, 10, 20, 30 0 56 10
13.03 EOL dual class 10A, 10, 20, 30 0 57 10A
13.04 EOL out
Eventgroup 0 ... 6
0 84 0000010
13.05 EOL operation Off, Stop-Manual, Stop-Automatic, Indication 0 227 Stop-Manual
13.06 Locked rotor level 0.5 ... 8.0 x
I
e
1 54 4.0 x I
e
13.07 Locked rotor trip time 0.20 ... 10.00 s 2 53 1.00 s
13.08 Locked rotor delay time 1.00 ... 30.00 s 2 52 5.00 s
13.09 Locked rotor out
Eventgroup 0 ... 6
0 85 0000010
13.10 Locked rotor op Off, Stop-Manual, Stop-Automatic, Indication 0 228 Off
13.11 Max no of starts per hour 1 ... 100 0 229 6
13.12 Max no of starts per hour
out
Eventgroup 0 ... 6
0 230 0000010
13.13 Max no of starts per hour
op
Off, Stop-Manual, Stop-Automatic, Indication 0 231 Off
7