138 Functions | Installation and commissioning manual | 1SFC132081M0201
Parameter
number
Description Setting range Number of
decimals
Fieldbus
ID
Default value Actual
setting
14 Protections list 2
14.01 Curr underload level 0.3 ... 0.9 x I
e
1 232 0.5 x I
e
14.02 Curr underload trip time 0 ... 10 s 0 233 10 s
14.03 Curr underload delay time 0 ... 30 s 0 234 5 s
14.04 Curr underload out
Eventgroup 0 ... 6
0 87 0000010
14.05 Curr underload op Off, Stop-Manual, Stop-Automatic, Indication 0 235 Off
14.06 Pwr factor underload level 0.00 ... 1.00 2 236 0.50
14.07 Pwr factor underload trip
time
0 ... 10 s 0 237 10 s
14.08 Pwr factor underload delay
time
0 ... 30 s 0 238 5 s
14.09 Pwr factor underload out
Eventgroup 0 ... 6
0 86 0000010
14.10 Pwr factor underload op Off, Stop-Manual, Stop-Automatic, Indication 0 239 Off
14.11 Curr imb level 10 ... 80% 0 61 80%
14.12 Curr imb trip time 1 ... 30 s 0 63 10 s
14.13 Curr imb delay time 1 ... 30 s 0 62 5 s
14.14 Curr imb out
Eventgroup 0 ... 6
0 64 0000010
14.15 Curr imb operation Off, Stop-Manual, Stop-Automatic, Indication 0 60 Off
15 Protections list 3
15.01 Over voltage level 170 ... 850 V 0 67 850 V
15.02 Over voltage trip time 0.1 ... 100.0 s 1 65 1.0 s
15.03 Over voltage out
Eventgroup 0 ... 6
0 68 0000010
15.04 Over voltage op Off, Stop-Manual, Stop-Automatic, Indication 0 66 Off
15.05 Under voltage level 165 ... 850 V 0 71 165 V
15.06 Under voltage trip time 0.1 ... 100.0 s 1 69 1.0 s
15.07 Under voltage op Off, Stop-Manual, Stop-Automatic, Indication 0 70 Off
15.08 Under voltage out
Eventgroup 0 ... 6
0 72 0000010
15.09 Voltage imb level 1 ... 100% 0 77 10%
15.10 Voltage imb out
Eventgroup 0 ... 6
0 78 0000010
15.11 Voltage imb op Off, Stop-Manual, Stop-Automatic, Indication 0 76 Off
15.12 Voltage imb trip time 1 ... 100 s 0 10 s
16 Protections list 4
16.01 Phase rev out
Eventgroup 0 ... 6
0 89 0000010
16.02 Phase rev operation Off, Stop-Manual, Stop-Automatic, Indication 0 240 Off
16.03 Freq range lower trip lvl 40 ... 72 Hz 0 241 45 Hz
16.04 Freq range upper trip lvl 40 ... 72 Hz 0 242 66 Hz
16.05 Freq range trip time 0.0 ... 60.0 s 1 243 5.0 s
16.06 Freq range out
Eventgroup 0 ... 6
0 91 0000010
16.07 Freq range operation Off, Stop-Manual, Stop-Automatic, Indication 0 244 Off
16.08 Bypass open out
Eventgroup 0 ... 6
0 95 0000010
16.09 Bypass open operation Off, Stop-Manual, Stop-Automatic, Indication 0 245 Indication
16.10 Voltage outputs out
Eventgroup 0 ... 6
0 - 0000010
16.11 Voltage outputs op Off, Stop-Manual, Stop-Automatic, Indication 0 - Indication
17 Protections list 5
17.01 PTC out
Eventgroup 0 ... 6
0 88 0000010
17.02 PTC op Off, Stop-Manual, Stop-Automatic, Indication 0 246 Off
17.03 PT100 2wire res 0 ... 100.0 Ω 1 247 5.0 Ω
17.04 PT100 trip temp -50 ... 250 °C 0 248 60 °C
17.05 PT100 reset temp -50 ... 250 °C 0 240 40 °C
17.06 PT100 out
Eventgroup 0 ... 6
0 98 0000010
17.07 PT100 op Off, Stop-Manual, Stop-Automatic, Indication 0 250 Off
7