1SFC132081M0201 | Installation and commissioning manual | Functions 141
Parameter
number
Description Setting range Number of
decimals
Fieldbus
ID
Default value Actual
setting
26.11 Faulty connection out Eventgroup 0 ... 6 0
282
0000001
26.12 Faulty connection op Stop-Manual, Stop-Automatic 0 283 Stop-Manual
27 Language
27.01 Language English, Spanish, Finnish, French, Italian
Dutch, Polish, Portuguese, Russian, Swedish
Turkish, Chinese (simplified Chinese), Arabic
Czech, German
0 173 English
27.02 Basic set-up at power on Yes, No 0 284 Yes
28 Service
28.01 ID Invalid ID, 30, 37, 45, 60, 72, 85, 105, 142, 170,
210, 250, 300, 370, 470, 570, 720, 840, 1050,
1250
0 171 -
28.02 Line contactor close time 0 ... 65535 ms 0 175 245 ms
28.03 TOR relay delay time 0.0 ... 300.0 s 1
286
0.0 s
28.04 Start without start command On / Off 0
287
Off
28.05 Step down level 10 ... 100% 0 9 80%
28.06 Torque profile start Constant setpoint, Linear ramp,
Progressive curve, High inertia curve
0 10 Linear ramp
28.07 Torque finish 30 ... 500% 0 17 100%
28.08 Torque tune 0 ... 1000% 0 11 100%
28.09 Torque ctrl gain 0.01 ... 10.00 2 12 0.02
28.10 Torque PI integration time 0.001 ... 10 s 3 13 0.004 s
28.11 Torque slip 0.1 ... 100% 1 14 1.0%
28.12 Torque diff 0.1 ... 100% 1 15 2.0%
28.13 Torque filter time 0.01 ... 100 s 2 16 0.02 s
28.14 Mains lock setting Automatic lock, 50 Hz manual lock
60 Hz manual lock
0
-
Automatic lock
28.15 Minimum trig time 0.0 ... 1.0 ms 3
-
0.208 ms
28.16 Accel adapt U start ramp On / Off 0
290
Off
28.17 U start ramp switch level 10 ... 100% 0
-
22%
28.18 T start ramp switch level 10 ... 100% 0
-
30%
28.19 Stop ramp switch level 10 ... 100% 0
-
52%
28.20 In-Line gain 0.0 ... 30.0 1
-
0.0
28.21 Inside delta gain 0.0 ... 30.0 1
-
3.0
28.22 Phase loss On / Off 0 - On
28.23 Phase loss during TOR On / Off 0
-
On
28.24 Phase loss trip time 20 ... 4000 ms 0 - 500 ms
28.25 Phase loss trip angle 1 1 ... 240 0
-
12
28.26 Phase loss trip angle 2 1 ... 240 0 - 70
28.27 Bad network quality On / Off 0 - On
28.28 Low supply voltage On / Off 0 - On
28.29 High current fault On / Off 0 - On
28.30 Shunt fault On / Off 0 - On
28.31 Short circuit thyristor On / Off 0 - On
28.32 Open circuit thyristor On / Off 0
-
On
28.33 Thyristor overload On / Off 0 - On
28.34 Heatsink over temp On / Off 0
-
On
28.35 Faulty connection On / Off 0
-
On
28.36 Faulty usage On / Off 0
-
On
28.37 Close bypass curr lvl 0.5 ... 4.0 x I
e
1 - 1.2 x I
e
28.38 Simulation motor M3AA 100L 2 (Ie = 5.2 A), M3BP 112M 4
(Ie = 7.4 A), M2AA 180MLA 6G (Ie = 29.3 A),
M2AA 180MLB 4G (Ie = 39.9 A), M3AA 250SMA
8 (Ie = 62.3 A), M3AA 200MLB 2 (Ie = 59.2 A),
M2AA 225SMA 2G (Ie = 74.7 A), M2BP 250SMA
4G (Ie 96.6 A), M2BA 280SMB 2L (Ie = 144.9 A),
M2BA 315SMB 4L (Ie = 221.8 A), M2BA
315MLA 2L (Ie = 319.6A), M4BP 200MLB 2G (Ie
= 59.3 A),
M3BP 315LKB 4K (Ie = 330.4 A), M3BP
315MLA 2M (Ie = 255.4 A),M3BP 280MLA 4M
(Ie 151.5 A),
M3BP 355SMC 6K (Ie = 325.6 A),
0 29 M3AA 250SMA
8
(Ie = 62.3 A)
7