1MRK 505 353-UEN Section 3
Configuring bay protection using HMI500
Application Manual 27
Bay protection functions REB500
Default
The “Default” tab lists station protection default outputs (see Figure 13). Any bina-
ry input of a BP function can be linked to these to enable the exchange of signals
between station protection and the bay protection sections (e.g. signal
21105_External TRIP).
Figure 13 Configuring binary inputs (“Default” à Output from SP function)
Location of input signals from ‘SP function’within the BP func-
tion diagram see Figure 1, Label No. 15.
General Purpose
The “General Purpose” tab provides facility for defining up to 20 user signals. To
this end, select a signal number with the left mouse button. A text field appears in
which the user can write a signal name (see Figure 14).
The signal name entered must conform to REB500 signal conventions (see Section
2.3.2.1). The Section 2.3.2.3 provides a list of all signals available for “General
Purpose” inputs.