1.1 Device identification Capabilities Current value If configurable, list
methods
1.1.12 DNP3 XML files
available off-line
Rd Wr Filename Description of contents Not supported
dnpDp.xml Complete device profile
dnpDPCap.xml Device profile capabilities
dnpDPCfg.xml Device profile config values
* The Complete Device Profile Document contains the
capabilities, Current Value, and configurable methods
columns.
*
The Device Profile Capabilities contains only the
capabilities and configurable methods columns.
* The Device Profile Config. Values contains only the
Current Value column.
1.1.13 Connections
supported
● Serial (complete section 1.2) Serial IP networking PST of LHMI
● IP networking (complete section 1.3)
○ Other, explain:
1.1.14 Conformance
Testing
Self-tested, version ________
Independently tested, version
Version 2.6 rev1 28
th
October 2010
Test organisation name
DNV GL
Table 3: Serial connections
1.2a Serial connections
Capabilities Current value If configurable, list
methods
1.2.1 Port name: Name
used to reference the
communication port
defined in this section
RS485 PST of LHMI
1.2.2 Serial connection
parameters
Asynchronous PST of LHMI
● Asynchronous - Data Bits, Start Bit, Stop Bit, Parity
○ Other, explain:
1.2.3 Baud rate ○ Fixed at 9600 PST of LHMI
(BaudRate)
● Configurable, range 300 to 115200
○ Configurable, selectable from _____,_____,_____
○ Configurable, other, describe:
1.2.4 Hardware flow control (Handshaking): Describe hardware signaling requirements of the interface. Where a transmitter or receiver is
inhibited until a given control signal is asserted, it is considered to require that signal before sending or receiving characters. Where a signal is
asserted before transmitting, that signal will be maintained active until after the end of transmission. Where a signal is asserted to enable
reception, any data sent to the device when the signal is not active could be discarded.
Table continues on next page
1MRK 511 419-UUS A Section 3
DNP3 protocol implementation
650 series 2.2 ANSI 29
Point list manual