This is done with a speed so that the final impedance is reached after 1s. As
the injected voltage is lower than 0.92 UBase the STAR
T signal should be
activated. In addition to this the signal ZONE2 should be activated.
7. Set N2Limit to 1 and repeat step
6.
Now the signals TRIP2 and TRIP should be activated.
IED
B A
E
B
E
A
X’
d
X
T
Z
S
Zone 1 Zone 2
jX
R
ZB
ZA
Pole slip
impedance
movement
Zone 2
Zone 1
WarnAngle
TripAngle
f
ZC
IEC07000099_2_en.vsd
IEC07000099 V2 EN-US
Figure 38: Setting of the pole slip protection PSPPPAM
Section 11 1MRK 505 378-UEN A
Testing functionality by secondary injection
148 Line differential protection RED670 2.2 IEC
Commissioning manual