9.4 Setting the TCP/UDP client communication
GUID-6CEE3261-D211-4051-8CA8-5840C27C560E v2
As an example of a TCP/UDP client, the openPDC tool (PMU Connection T
ester
V
er. 4.2.12) from Grid Protection Alliance is used in this section. Install PMU
Connection Tester tool on a PC with Ethernet network adaptor available. The same
PC used for PCM600 can be used to install the PMU Connection Tester tool.
IEC140000133 V1 EN-US
Figure 9: PMU Connection Tester tool
The following steps explain how to set the PMU Connection Tester parameters in
order to establish an IEEE C37.118 connection with the PMU:
1. Set the IP stack on PMU Connection Tester to IPv4. Note that the default IP
stack on PMU Connection Tester tool is IPv6.
1MRK 505 378-UEN A Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
Line differential protection RED670 2.2 IEC 75
Commissioning manual