1.1. Navigate to the Settings
tab.
1.2. Force the IP stack to IPv4 by setting the parameter ForceIPv4 to True.
2. Set the Connection Parameters on PMU Connection Tester for TCP
communication according to the PMU configuration.
IEC140000135-1-en.vsd
IEC140000135 V1 EN-US
2.1. Set
Host IP to the PMU IP address configured for the port in use. Here
the LANAB:1 IPAddress (192.168.1.10) is set.
2.2. Set Port to the IED's TCP port set in the PMU under parameter
C37.118TCPport (4712 is default). Alternatively, in order to make an
Section 9 1MRK 505 378-UEN A
Establishing connection and verifying the IEEE C37.118/1344 communication
76 Line differential protection RED670 2.2 IEC
Commissioning manual