IEEE1344 communication, the 1344TCPport parameter setting can be
used (4713 is default).
2.3. Set the
Protocol as IEEE C37.118.2-2011.
2.4. Set the Device ID Code in PMU Connection Tester per PMU Data
Stream ID Number (IDCODE). The PMU Data Stream ID Number is a
user assigned ID number (1-65534) for each data stream sent out from
the PMU and it is defined under parameter PMUdataStreamIDCODE.
(Main menu/Configuration/Communication/Station
communication/phasor measurement/PMU Report/PMUREPORT:
1)
2.5. Make sure that the Configure Alternate Command Channel is set as Not
Defined. The Configure Alternate Command Channel is used to
configure a TCP channel to control the UDP data communication and
transfer the header, configuration and command frames.
2.6. Continue to the section
Verifying the IEEE C37.118/1344 TCP
communication.
3. Set the Connection Parameters on PMU Connection T
ester for UDP
communication according to the PMU configuration.
IEC140000136 V1 EN-US
3.1. Set the
Local Port to UDP destination port defined in the PMU under
the parameter UDPDestPort1 (Default value: 8910).
3.2. Click the Configure Alternate Command Channel to configure the
TCP channel. A new window will pop up. A TCP channel needs to be
configured in order to control the UDP data communicatiuon and
transfer the header, configuration and command frames.
1MRK 505 378-UEN A Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
Line differential protection RED670 2.2 IEC 77
Commissioning manual