EasyManua.ls Logo

ABB RED670 - Page 157

ABB RED670
308 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
If the rated secondary current I
rs
of the analog channel is 1 A, then the maximum
current test I
ts
is
I I I A
ts ovrl rs
= × =4 4
EQUATION14041 V1 EN-US (Equation 4)
If the CT of the generator has ratio 9000/1 A, then in primary values
I I I
I
I
A
t ovrl p ovrl
rp
rs
= × = × =
,
4
9000
1
36000
EQUATION14042 V1 EN-US (Equation 5)
Reference is made to the numerical values of the example, explained in the
“Setting guidelines” of the Application Manual. A test current equal to 2.5 time the
base current of the generator is chosen; this choice is related to the selected test
voltage that is applied while testing the point SE and RE.
I I A
t Base
= × = × =2 5 2 5 8367 20918. .
EQUATION14043 V1 EN-US (Equation 6)
The parameter ReachZ1 defines the boundary between zone 1 and zone 2; it is
expressed in percent of the parameter ForwardX
. If the setting of ReachZ1 = 12%,
then corresponding primary value of the reactance is
X
ReachZ ForwardX
ZBase
RZ 1
1
100 100
12
100
59 33
100
0 9522 0= × × = × × =
.
. .0068
EQUATION14044 V1 EN-US (Equation 7)
The calculation of the test voltage, that is related to ReachZ1, is based on the
impedance Z
RZ1
that has imaginary part X
RZ1
and real part R
RZ1
:
RRZ
achZ ForwardR
ZBase1
1
100 100
12
100
8 19
100
0 9522 0 0= × × = × × =
Re .
. . 009
EQUATION14045 V1 EN-US (Equation 8)
The magnitude of the impedance Z
RZ1
is:
2 2 2 2
1 1 1
0.009 0.068 0.069
RZ RZ RZ
Z R X= + = + = W
EQUATION14046 V1 EN-US (Equation 9)
Hence the reference voltage of the test of the boundary between zone 1 and zone 2
is
V Z I V
t RZ RZ t,
.
1 1
0 069 20918 1435= × = × =
EQUATION14047 V1 EN-US (Equation 10)
If the test voltage is lower than V
t,RZ1
(or in opposition), then the test is related to
the zone 1; if the test voltage is higher than V
t,RZ1
, then the test is related to the
zone 2.
1MRK 505 378-UEN A Section 11
Testing functionality by secondary injection
Line differential protection RED670 2.2 IEC 151
Commissioning manual

Table of Contents

Other manuals for ABB RED670

Related product manuals