EasyManua.ls Logo

ABB RED670 - Page 159

ABB RED670
308 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
calculated by using a factor 2.5 (instead of the maximum value 4) in order to
reduce the magnitude of the test voltage for the points RE and SE.
Test sets usually do not have a feature to simulate a real network during a power
swing and apply the related analog quantities at the terminal of the generator. The
scope of the present test is not a simulation of a real network. Voltages and currents
are supplied in order to measure an impedance that changes in the time and
traverses the plane R-X and, in particular
, the area inside the lens characteristic.
The test may be performed by applying:
Symmetric three-phase voltage at 50 Hz. The magnitude depends on the point
of the characteristic that needs to be verified. The following three main points
of the line segment SE-RE need to be checked:
the point RE (R
FwdR
, X
FwdX
)
a point which is related to the parameter ReachZ1 (boundary between
zone 1 and zone 2)
the point SE (R
RvsR
, X
RvsX
)
The phase angle of the test voltages is equal to:
arctan (ForwardX/ForwardR) for tests in the quadrant 1 and 2 of the R-X
plane
arctan (ReverseX/ReverseR) -180° for tests in the quadrant 3 and 4 of the R-X
plane
Symmetric three-phase current, where the current is the summation of two
currents that have the same magnitude, but different frequencies.
I I A
tf
t
I
50
2
20918
2
10459= = = =
GUID-F02E8D18-FF87-45BE-8142-E8FA19F6966B V1 EN-US (Equation 19)
The first current I
50
has frequency 50 Hz, magnitude 10459 A (that is, 1.162 A
secondary) and phase angle 0º.
The second current I
tf
has magnitude 10459 A (that is, 1.162 A secondary),
phase angle 180º (at the starting time of the test) and frequency:
49.5 Hz for the test as generator in the quadrant 1 and 2 of the R-X plane
50.5 Hz for the test as generator in the quadrant 3 and 4 of the R-X plane
When the trajectory of the impedance, that is seen by the protection
function, traverses the lens characteristic then a pole slipping is
detected. The present procedure avoids tests of points of the line
SE-RE that are too close to the R-axis because in that case the
voltage is close to zero and, therefore, the impedance may approach
a not defined quantity 0/0.
1MRK 505 378-UEN A Section 11
Testing functionality by secondary injection
Line differential protection RED670 2.2 IEC 153
Commissioning manual

Table of Contents

Other manuals for ABB RED670

Related product manuals