5. Measure the operate time of the timer by injecting 1.2 · UNRel> and a current
to get two times the set SN> operate value.
( )
0 0/ 3 3 costest testTinv kSN Sref I U
j
= × × ×
IECEQUATION2403 V1 EN-US (Equation 81)
6. Compare the result with the expected value.
The expected value depends on whether definite or inverse time was selected.
7. Continue to test another function or complete the test by setting the test mode
to
Off.
Operation mode 3I
0
and φ
SEMOD175060-87 v8
1. Set the polarizing voltage to 1.2 · UNRel> and set the phase angle between
voltage and current to the set characteristic angle (RCADir). Note that the
current lagging the voltage.
2. Inject current until the function picks up, and make sure that the operate
current is equal to the INDir> setting for the set directional element.
Note that for operation, both the injected current and voltage
must be greater than the set values INRel> and UNRel>
respectively.
The function activates the ST
ART and STDIRIN output.
3. Measure with angles j around RCADir +/- ROADir
.
4. Compare the result with the set values, refer to figure 45 for example
characteristic.
5. Measure the operate time of the timer by injecting a current to get two times
the set
SN_> operate value.
( )
0 0/ 3 3 costest testTinv kSN Sref I U
j
= × × ×
IECEQUATION2403 V1 EN-US (Equation 82)
6. Compare the result with the expected value.
The expected value depends on whether definite or inverse time was selected.
7. Continue to test another function or complete the test by setting the test mode
to
Off.
1MRK 505 378-UEN A Section 11
Testing functionality by secondary injection
Line differential protection RED670 2.2 IEC 181
Commissioning manual