EasyManua.ls Logo

ABB RED670 - Page 203

ABB RED670
308 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The operate value in secondary volts is calculated according
to the following equations:
For phase-to-earth measurement:
U UBase VT
VTprim
1
100
3
<
× ×
sec
IECEQUATION2430 V1 EN-US (Equation 97)
For phase-to-phase measurement:
U
UBase
VT
VTprim
1
100
<
× ×
sec
IECEQUATION2431 V1 EN-US (Equation 98)
5. Increase the measured voltage to rated load conditions.
6. Check that the
START signal resets.
7. Instantaneously decrease the voltage in one phase to a value about 20% lower
than the measured operate value.
8. Measure the time delay for the TRIP signal, and compare it with the set value.
9. Check the inverse time delay by injecting a voltage corresponding to 0.8 ×
U1<.
For example, if the inverse time curve A is selected, the trip
signals TR1 and TRIP operate after a time corresponding to
the equation:
t s
k
U
U
( )
=
<
1
1
1
IECEQUATION2428 V1 EN-US (Equation 99)
where:
t(s) Operate time in seconds
k1 Settable time multiplier of the function for step 1
U Measured voltage
U1< Set start voltage for step 1
For example, if the measured voltage jumps from the rated value to 0.8 times
the set start voltage level and time multiplier k1 is set to 0.05 s (default
value), then the TR1 and TRIP signals operate at a time equal to 0.250 s ±
tolerance.
10.
The test above can be repeated to check the inverse time characteristic at
dif
ferent voltage levels.
11. Repeat the above described steps for Step 2 of the function.
1MRK 505 378-UEN A Section 11
Testing functionality by secondary injection
Line differential protection RED670 2.2 IEC 197
Commissioning manual

Table of Contents

Other manuals for ABB RED670

Related product manuals