Test for fast fault clearing
Connect the test set for the injection of three phase voltages and currents to the
appropriate terminals of the IED.
Enable the fast fault clearance by setting FastOperation to TRUE, and also
connect the inputs BLKDLFLT to TRUE and FUSEFAIL to FALSE.
Also assume circuit breaker is in closed position, that is CBCLOSED is high,
prior to fault occurrence.
Create a single phase fault on phase L1 such that phase L1 voltage is lower
than UPhSel< times quadrature phase to phase voltage and set Tau to default
value.
Activate carrier receive CR signal.
Check that TRIP, TRL1, ARST and ARSTL1 are generated with the
conditions described.
Check that activated trip signals and start signals are blocked by enabling
BLKTR and BLKST.
Check that all activated signals are disabled by BLOCK input.
If required, perform creating faults on the remaining phases in the similar way.
Test of delayed fault clearing for single pole tripping
Connect the test set for the injection of three phase voltages and currents to the
appropriate terminals of the IED.
Enable the delayed fault clearance for single pole tripping by setting
Del1phOp to 1Ph (On), Del3PhOp to FALSE (Off) and also connect the inputs
BLKDLFLT and FUSEFAIL to FALSE.
Also assume circuit breaker is in closed position, that is input CBCLD is high,
prior to fault occurrence.
Create a single phase fault on phase L1 such that phase L1 voltage is lower
than UPhSel< times quadrature phase to phase voltage and set Tau to default
value and also inject the residual current such that it exceeds set IN> value.
Check that output TRIN is activated after a set delay of tResCurr if
ResCurrOper is set to high.
Check that TRIP and TRL1 are generated with the conditions described after a
set delay time of t1Ph and the outputs ARST and ARSTL1 are also activated. .
Check that activated trip signals and start signals are blocked by enabling
BLKTR and BLKST.
Check that all activated signals are disabled by BLOCK input.
If required, perform creating faults on the remaining phases in the similar way.
Test of delayed fault clearing for three pole tripping
Connect the test set for the injection of three phase voltages and currents to the
appropriate terminals of the IED.
Enable the delayed fault clearance for three pole tripping by setting Del3phOp
to TRUE (On), Del1PhOp to 3Ph (Off) and also connect the inputs BLKDLFLT
and FUSEFAIL to FALSE.
Also assume circuit breaker is in closed position, that is, the input CBCLOSED
is high prior to fault occurrence.
1MRK 505 378-UEN A Section 11
Testing functionality by secondary injection
Line differential protection RED670 2.2 IEC 207
Commissioning manual