Headline Explanation
Invalid value set for PMU Parameters There are two explanations possible:
Check if the following parameters are set
correctly on PMUREPORT:
ReportRate
or
SvcClass
or parameter PRIMVAL:
1.FrequencySel is not set as 50Hz / 60Hz.
Check if the following parameters are set
correctly on PMUREPORT:
ReportRate
or
SvcClass
or
RptTimetag
or parameter PRIMVAL:
1.FrequencySel is not set as 50Hz / 60Hz.
Invalid phase angle reference The selected
PhaseAngleRef
corresponds to an
analog channel that is not configured. Please
configure a valid reference channel.
GOOSE is configured on a disabled port At least one of the access points configured for
GOOSE is disabled. The port can be disabled
either through changing the access point
operation to off or by unchecking the GOOSE
protocol from the access point in the Ethernet
configuration in PCM600 or LHMI.
Please enable GOOSE on access points:
AP_FRONT, AP_1
LDCM not running the application image <slot number> is running the factory image
instead of the application image. The factory
image is older and does not contain the latest
updates and fixes.
Please reboot the IED. If the problem persists
update the LDCM firmware or replace the board.
LDCM version is not accepted <device name> firmware version <version
string> is not accepted. The minimum accepted
version is <version string>.
Please update the LDCM firmware or replace the
board.
OEM not running the application image OEM in slot <slot number> is running the factory
image instead of the application image. The
factory image is older and does not contain the
latest updates and fixes.
Please reboot the IED. If the problem persists,
update the OEM firmware or replace the board.
SFP unplugged from the slot SFP has been unplugged from the slot
Please check the connection.
Corresponding hardware(s) is set to fail.
SFP replaced with other type Configured and the detected SFP(s) are
different. Corresponding hardware(s) is set to
fail.
Please restart IED and consider Reconfigure HW
modules to get updated hardware list.
Non ABB vendor SFP detected Non ABB vendor SFP detected.
Corresponding hardware(s) is set to fail. Please
use ABB approved SFP’s.
Section 14 1MRK 505 378-UEN A
Troubleshooting
288 Line differential protection RED670 2.2 IEC
Commissioning manual