Section 6 1MDU07212-YN Rev. C
Installation
66 REF601 / REJ601
Application Manual
Table 29: Settings, continue
Parameter
Actual
value
Default
value
Unit Range Resolution
3Ith> / 49
ϑ0
080 % 0.0…100% 1%
ϑpowerOFF
4 - 1…4 1
Ib 1.0 In 0.1 … 1.5 0.100
τ
045 min 1.0…300 1.000
τs
045 min 1.0…300 1.000
ϑalm
121 % 50…200%, 1%
ϑtrip
144 % 50…200%, 1%
ϑstartinhibit
105 % 50…200%, 1%
3I/IoBF / 51BF/51NBF
Icbfp 01.1 In 0.2…2.0 0.100
Iocbfp 01.1 In 0.1…2.0 0.100
t Retrip 0.10 s 0.06…0.5 0.010
t Backup 0.12 s 0.06…0.5 0.010
O -> I / 79
AR start
mode
1
-
1 = Trip, 2 = Gen. start and trip 1
CB ready 1
-
1 = OCO, 2 = CO 1
Shot 3
-
0…4 1
Activate t sec 0.1…5 0.100
Pulse tp sec 0.2…20 0.100
Cycle t1 sec 0.2…300 0.010
Cycle t2 sec 0.2…300 0.010
Cycle t3 sec 0.2…300 0.010
Cycle t4 sec 0.2…300 0.010
Reclaim tr sec 1…300 1
Block tb sec 1…300 1