Table 58: X130 (RTD/mA) monitored data
Name Type Values (Range) Unit Description
AI_DB1 FLOAT32 -10000.0...10000
.0
mA input, Connectors
1-2, reported value
AI_RANGE1 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
mA input, Connectors
1-2, range
AI_DB2 FLOAT32 -10000.0...10000
.0
mA input, Connectors
3-4, reported value
AI_RANGE2 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
mA input, Connectors
3-4, range
AI_DB3 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
5-6-11c, reported value
AI_RANGE3 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
5-6-11c, range
AI_DB4 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
7-8-11c, reported value
AI_RANGE4 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
7-8-11c, range
AI_DB5 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
9-10-11c, reported value
AI_RANGE5 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
9-10-11c, range
AI_DB6 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
13-14-12c, reported
value
AI_RANGE6 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
13-14-12c, range
AI_DB7 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
15-16-12c, reported
value
Table continues on next page
Section 3 1YHT530004D05 D
Basic functions
96 615 series
Technical Manual

Table of Contents