EasyManua.ls Logo

ABB REF615 E - Technical Data

ABB REF615 E
896 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 305: DEFHPDEF Monitored data
Name Type Values (Range) Unit Description
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
DIRECTION Enum 0=unknown
1=forward
2=backward
3=both
Direction information
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between operating
angle and characteristic
angle
ANGLE FLOAT32 -180.00...180.00 deg Angle between
polarizing and operating
quantity
I_OPER FLOAT32 0.00...40.00 Calculated operating
current
DEFHPDEF Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.2.2.13 Technical data
Table 306: DEFxPDEF Technical data
Characteristic
Value
Operation accuracy Depending on the frequency of the current
measured: f
n
±2 Hz
DEFLPDEF
Current:
±1.5% of the set value or ±0.002 x I
n
Voltage
±1.5% of the set value or ±0.002 x U
n
Phase angle:
±2°
DEFHPDEF Current:
±1.5% of the set value or ±0.002 x I
n
(at currents in the range of 0.1…10 x I
n
)
±5.0% of the set value
(at currents in the range of 10…40 x I
n
)
Voltage:
±1.5% of the set value or ±0.002 x U
n
Phase angle:
±2°