Table 187: PH3IPTOC Non group settings
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Num of start phases 1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases required for operate
activation
Reset delay time 0...60000 ms 10 20 Reset delay time
4.1.2.9 Monitored data
Table 188: PH3LPTOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
PH3LPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 189: PH3HPTOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
PH3HPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 190: PH3IPTOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
PH3IPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1YHT530004D05 D Section 4
Protection functions
615 series 175
Technical Manual