Table 603: ESSXSWI Input signals
Name Type Default Description
POSOPEN BOOLEAN 0=False
Signal for open position of apparatus from I/O
1)
POSCLOSE BOOLEAN 0=False
Signal for closed position of apparatus from I/O
1)
1) Not available for monitoring
Table 604: DCSXSWI Output signals
Name Type Description
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
OKPOS BOOLEAN Apparatus position is ok
Table 605: ESSXSWI Output signals
Name Type Description
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
OKPOS BOOLEAN Apparatus position is ok
9.2.7 Settings
Table 606: DCSXSWI Non group settings
Parameter
Values (Range) Unit Step Default Description
Event delay 0...10000 ms 1 100 Event delay of the intermediate position
Table 607: ESSXSWI Non group settings
Parameter
Values (Range) Unit Step Default Description
Event delay 0...10000 ms 1 100 Event delay of the intermediate position
9.2.8 Monitored data
Table 608: DCSXSWI Monitored data
Name
Type Values (Range) Unit Description
POSITION Dbpos 0=intermediate
1=open
2=closed
3=faulty
Apparatus position
indication
Section 9 1YHT530004D05 D
Control functions
678 615 series
Technical Manual