EasyManua.ls Logo

ABB REF615 E - Page 64

ABB REF615 E
896 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 34: X130 BIO binary input settings
Parameter Values (Range) Unit Step Default Description
Input 1 filter time 5...1000 ms 5 Connectors 1-2c
Input 2 filter time 5...1000 ms 5 Connectors 3-2c
Input 3 filter time 5...1000 ms 5 Connectors 4-5c
Input 4 filter time 5...1000 ms 5 Connectors 6-5c
Input 5 filter time 5...1000 ms 5 Connectors 7-8c
Input 6 filter time 5...1000 ms 5 Connectors 9-8c
Input 1 inversion 0=False
1=True
0=False Connectors 1-2c
Input 2 inversion 0=False
1=True
0=False Connectors 3-2c
Input 3 inversion 0=False
1=True
0=False Connectors 4-5c
Input 4 inversion 0=False
1=True
0=False Connectors 6-5c
Input 5 inversion 0=False
1=True
0=False Connectors 7-8c
Input 6 inversion 0=False
1=True
0=False Connectors 9-8c
Table 35: X130 AIM binary input signals
Name
Type Description
X130-Input 1 BOOLEAN Connectors 1-2
X130-Input 2 BOOLEAN Connectors 3-4
X130-Input 3 BOOLEAN Connectors 5-6
X130-Input 4 BOOLEAN Connectors 7-8
Table 36: X130 AIM binary input settings
Parameter
Values (Range) Unit Step Default Description
Input 1 filter time 5...1000 ms 5 Connectors 1-2
Input 2 filter time 5...1000 ms 5 Connectors 3-4
Input 3 filter time 5...1000 ms 5 Connectors 5-6
Input 4 filter time 5...1000 ms 5 Connectors 7-8
Input 1 inversion 0=False
1=True
0=False Connectors 1-2
Input 2 inversion 0=False
1=True
0=False Connectors 3-4
Input 3 inversion 0=False
1=True
0=False Connectors 5-6
Input 4 inversion 0=False
1=True
0=False Connectors 7-8
Section 3 1YHT530004D05 D
Basic functions
58 615 series
Technical Manual

Table of Contents

Related product manuals