ABB REF615 K - Page 440

ABB REF615 K
896 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
s1s2
s1
s2
VDR
Stabilizing
Resistor
High impedance
protection
(HREFPDIF)
GUID-367BDBC9-D2E8-48D3-B98F-623F7CD70D99 V3 EN
Figure 233: Connection scheme for the restricted earth-fault protection
according to the high-impedance principle
High-impedance principle
High-impedance principle is stable for all types of faults outside the zone of
protection. The stabilization is obtained by a stabilizing resistor in the differential
circuit. This method requires that all the CTs used have a similar magnetizing
characteristic, same ratio and relatively high knee point voltage. CTs on each sides
are connected in parallel along with a relay-measuring branch as shown in
Figure
234. The measuring branch is a series connection of stabilizing resistor and IED.
Section 4 1YHT530004D05 D
Protection functions
434 615 series
Technical Manual