Automatic reclosing function (AR) &KDSWHU
9HULI\LQJVHWWLQJVE\VHFRQGDU\
LQMHFWLRQ
 &KHFNWKHRSHUDWLRQLQVWDQGE\PRGH
Depending on the program selection and the selected fault types
that start and inhibit reclosing, a check of no unwanted reclosing
can be made. For example, if only single-phase reclosing is select-
ed, a test can verify that there is no reclosing after two-phase and
three-phase trips.
 7HVWLQJWKHPXOWLEUHDNHUDUUDQJHPHQW
If a multi-breaker arrangement is used for the application and priorities are given for the
master (high) and slave (low) terminals, test that correct operation takes place and that
correct signals are issued. The signals WFMASTER, UNSUC, WAIT and INHIBIT
should be involved.
 &RPSOHWLQJWKHWHVW
After the test, restore the equipment to normal or desired state. Especially check these
items:
 &KHFNDQGUHFRUGWKHFRXQWHUFRQWHQWV5HVHWLILWLVWKHXV
HU¶VSUHIHUHQFH
The counters menu is located in the local HMI under:
6HUYLFH5HSRUW)XQFWLRQV$XWR5HFORVHU$XWR5HFORVHUQ&RXQWHUV&OHDU
&RXQWHUV
 5HVHWWKHVHWWLQJSDUDPHWHUVDVUHTXLUHG
 'LVFRQQHFWWKHWHVWVZLWFKRUGLVFRQQHFWHGOLQNVRIFRQQHF
WLRQWHUPLQDOV
 5HVHWLQGLFDWLRQVDQGHYHQWV
The ClearDistRep menu is located in the local HMI under:
'LVWXUE5HSRUW&OHDU'LVW5HS
 &RPSOHWLQJWKHWHVW
Continue to test another function or complete the test by setting the test mode to off.
Restore connections and settings to the original values, if they were changed for testing
purpose.