EasyManua.ls Logo

ABB REL301 - Page 109

ABB REL301
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I.L. 40-386.3
5-2 (10/94)
Acceptance Test
Before beginning any testing, verify that voltage selectable input, and contact config-
uration jumpers are in the correct position. The following tables, with appropriate ref-
erence figures, will provide a guide for the jumper settings. In-service settings may
vary according to specific applications.
Filter Module
See Figure 5-1
for Location
Jumper Identification Jumper Purpose Factory Setting
P2 52 a Input Voltage Selection 48/125 Vdc
P18 52 b Input Voltage Selection 48/125 Vdc
P7 External Reset Input Voltage Selection 48/125 Vdc
P9 Pilot Enable Input Voltage Selection 48/125 Vdc
P10 Receiver 1 Input Voltage Selection 48/125 Vdc
P12 Sync-Check Voltage Reference VA
P13 Receiver 2 Input Voltage Selection 48/125 Vdc
Table 5-1:
Power Supply Module See Figure 5-2 for Location
Jumper Identification Jumper Purpose Factory Setting
JMP1 Carrier Stop Normally Open NO
JMP2 Carrier Send Normally Open NO
JMP5 Output contact 4 Normally Open NO
JMP4 Output Contact 3 Normally Open NO
JMP3 Output Contact 2 Normally Open NO
JMP6 Relay Fail Alarm AL1 Normally Closed NC
JMP7 Relay Trip Alarm AL2 Normally Open NO
Table 5-2:
Microprocessor Module * See Figure 5-3 for Location
Jumper Identification Jumper Purpose Factory Setting
JP3 Spare Jumper Storage IN (Jumper Present)
JP4 Trip Dropout Delay OUT (No Jumper)
JP5 Enable Output Test OUT (No Jumper)
JP6 A/D Calibration OUT (No Jumper)
* To verify or change jumper positions on the microprocessor module it is
necessary to remove the front panel of the REL 301/302.
Table 5-3:

Related product manuals