I.L. 40-386.3
3-14 (10/94)
field. The REL 301/302 clock will start at the time the enter button is pushed while
the display is showing the minute value.
3.4. RECLOSE INITIATION MODE PROGRAMMING
3.4.1 For Non-pilot and Pilot Systems
1. Select RI Type = OFF, 1PR, 2PR or 3PR, (See Table 3-2)
2. Use one of the two (RI-1 or RI-2) output contacts for the reclosing initiation circuit
3. Select one or all of the Fast RI, Zone2 RI, and/or Zone3 RI to YES, depending on the ap-
plication. (
Pilot System Only: For reclose initiation, following Pilot tripping,
Fast RI
should
be set to either
Pilot or Pilot/Z1/Inst I
)