I.L. 40-386.3
1-2 (10/94)
1. 2. REL 301/302 FEATURES
1.2.1 Standard Features for REL 301 (Non-Pilot)
3-Zone distance phase and ground relay, with reversible Zone3 phase and ground;
4 impedance units per zone: 3 phase-to-ground; 1 phase-to-phase.
T1 timer (0 to 15 cycles)
Independent timers for phase and ground
Overcurrent supervision of phase and ground distance
Selectable Zone2 torque controlled overcurrent (phase or ground)
Inverse time directional or non-directional (selectable) overcurrent ground backup
logic
Loss of potential supervision
Loss of current monitoring
Instantaneous forward directional phase and ground high set overcurrent trip
Close Into Fault Trip
Unequal-pole-closing load pickup logic
Selectable Loss-of-Load accelerated trip logic
Selectable Zone1 extension
Current change fault detector (I)
Voltage change fault detector (V)
Fault data can be re-accessed by moving down to the Last Fault or Previous Fault
display mode
Line voltage, current and phase angle monitoring
Selectable polarizing for directional overcurrent ground units (zero sequence, nega-
tive sequence and dual
Programmable Reclose initiation and reclose block outputs
100% Numerical processing
Fault location capability
Self-checking software
Breaker trip circuit test
Push-to-close test for output contacts
Binary input test of contact input circuits
Software switches for functional tests, e.g., (Carrier Send and Carrier Receivers)
Trip contact sealed in by trip current, and selectable dropout delay of 0 or 50 ms
16 fault records with setting selectable data capture choices which trigger fault re-
cording
Real-time clock
Low voltage pickup setting for weakfeed logic and close into fault trip
Setting positive sequence to zero sequence ratio
Double blinder logic for out of step blocking
RS-232C PONI or INCOM/PONI
16 sets of oscillographic data and intermediate target data. Each set includes 7 an-
alog graphic inputs and 24 digital. Each oscillographic target contains 1 prefault
and 7 fault cycles of data. Data collection can be started by TRIP, Z2 and trip, Z2Z3
and trip or V I