be blocked. This condition will be indicated with a sub-menu under Hints, where details about
this condition are shown. The Hint menu is a way to assist the user in troubleshooting.
The Hint menu is currently only available in English. All the entries are in English,
regardless of which language is selected.
The supported list of hints are as follows:
Table 19: Hint menu
Headline Explanation
Incorrect setting of SyncLostMode There are two explanations possible:
SyncLostMode
is set to
Block
, no time source is
configured to achieve the required accuracy. Unless a
high accuracy time source is selected, the function
dependent on high time accuracy will be blocked.
SyncLostMode
is set to
BlockOnLostUTC
, but there is
no UTC capable synch source (GPS, IRIG-B) used.
Unless a UTC capable time source is selected, the
function dependent on high time accuracy will be
blocked.
Sampled value substituted <Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID:
<ABB_MU0101>
Time diff: IED vs Sampled value <Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID:
<ABB_MU0101>
Frequency diff: IED vs Sampled value <Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID:
<ABB_MU0101>
Wrong cycle time for PMU report Wrong cycle time on SMAI or 3PHSUM block
connected to Phasor Report block. The SMAI or
3PHSUM block should have the same cycle time as
that of Phasor Report.
PMU not connected to 3ph output The PMU phasor report input(s) must be connected
to the 3ph output of SMAI or 3PHSU.
Invalid value set for PMU Parameters There are two explanations possible:
Check if the following parameters are set correctly on
PMUREPORT:
ReportRate
or
SvcClass
or parameter
PRIMVAL:1.FrequencySel is not set as 50Hz / 60Hz.
Check if the following parameters are set correctly on
PMUREPORT:
ReportRate
or
SvcClass
or
RptTimetag
or parameter PRIMVAL:1.FrequencySel is not set as
50Hz / 60Hz.
Invalid phase angle reference The selected
PhaseAngleRef
corresponds to an
analog channel that is not configured. Please
configure a valid reference channel.
GOOSE is configured on a disabled port At least one of the access points configured for
GOOSE is disabled. The port can be disabled either
through changing the access point operation to off
or by unchecking the GOOSE protocol from the
access point in the Ethernet configuration in PCM600
or LHMI.
Please enable GOOSE on access points: AP_FRONT,
AP_1
Table continues on next page
1MRK 500 127-UEN D Section 9
Troubleshooting
670 series 79
Operation manual