EasyManua.ls Logo

ABB Relion 670 series - IED (Intelligent Electronic Device)

ABB Relion 670 series
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LHMI info Description
Setting/signal Normal
(example)
Faulty
(example)
Specification
CommStatus OK NoRXD Status Communication status/no of
received messages
COMFAIL 0 1 Status Communication failure, differential
protection blocked. Analog values
are substituted with zero, ref.
disturbance recorder
COMALM
0 1 Status Communication alarm
(COMFAIL>set delay 100 ms in
service, 5-10 ms for fault tracing)
NoOfTXD
100.00 > 100 Status % No of sent messages
NoOfRXD 100.00
> 75
1)
Status % No of received messages
TransmDelay in
Echo mode 1)
2 ms - Time Round trip delay/2 + set asymmetric
delay
Transmission
delay in GPS
mode 1)
2 ms
- Time Actual transmission delay +
measured asymmetric delay (+or -)
AsymDelay 1) 0.5 ms - Setting / GPS
ms
Asymmetric delay (Setting in echo
mode or measured with GPS timing)
OPTPOWER –14.895 dBm Value Measured received optical power
BLKDIFF 0 1 Status Differential protection blocked by
communication
ADDRERR 0 1 Status Incoming message from a non-valid
address
RxAddress 2 ≠ 2 Received address from remote end
ConfAddress 2 - Configured remote address
RED_ACT 0/1 - Status Redundant channel 0=inactive
1=active
CRCERROR 0 1 Status CRC error in incoming message
TRDELERR 0 1 Status Transmission delay error, > 40 ms
SYNCERR 0 1 Status Error in echo timing synchronization
REMBLKDF 0 1 Status Error in received message at remote
end
GPSERROR 0 1 Status Error in GPS synchronization at
local or remote end
NOCARR 0 1 Status No carrier is detected in the
incoming message. Group signal -
Logical OR for:
LINK_LOST (no input data
stream at the optical receiver)
SYNC_LOST (clock
synchronization is lost)
C37 ERROR (error at the
C37.94 fiberoptic receiver:
faulty format)
NOMESS 0 1 Status No start and stop flags in the
incoming message
Table continues on next page
Section 5 1MRK 505 382-UEN B
Communication set-up
96 Communication set-up 670/650 series 2.2
Application Guide

Table of Contents

Other manuals for ABB Relion 670 series